Simulation-Based Voltage Drop Mitigation in a 20 kV Distribution Network Using Conductor Uprating Base on ETAP 12.6
DOI:
https://doi.org/10.69693/sustainable.v1i1.2Keywords:
Drop voltage, Uprating, Konduktor, Single Line DiagramAbstract
At PT PLN (Persero) UP3 Palembang, especially the Kenten area in the feeder distribution system, there has been a drop voltage and is almost close to the applicable standard threshold. So preventive efforts are needed so that the drop voltage situation does not worsen. It was recorded that there had been the highest drop voltage in the Beo feeder by 3.05%, in the Kacer feeder by 2.6%, the Pipit feeder by 2.35%, the Merak feeder by 2.3%, and the Foil feeder by 2.3%. This is a problem that should be able to be improved. In this study, a simulation of drop voltage repair will be carried out with the help of ETAP 12.6 software, which will describe a single line diagram with the results of load flow analysis in the form of drops that occur, with the authenticity of the data obtained as the simulation results show the real state of the field. In the simulation of repairing the drop voltage using the Conductor Uprating method for the repair of the drop that occurred in the feeder, after the repair was made, the drop voltage that occurred decreased in the Beo feeder by 1.705%, in the Kacer feeder by 1.69%, the Pipit feeder by 1.48%, the Merak feeder by 1.315%, and the Foil feeder by 1.24%.
Downloads
References
[1] Baqaruzi, S., & Muhtar, A. (2020). Analysis of Voltage Drops and Losses Due to the Effect of the Use of Distributed Generation in the 20 KV Primary Distribution System. E-JOINT (Electronica and Electrical Journal of Innovation Technology), 1(1), 20–26.
[2] Dat, H. T., Bich Tuyen, N. T., Binh, L. Q., Phuc Diem, N. N., & Tinh Minh, L. T. (2021). Evaluation and Improvement of the Reliability of the actual distribution network using ETAP. Proceedings - 2021 International Symposium on Electrical and Electronics Engineering, ISEE 2021, 193–198.
[3] Istiana Handayani, F., & Nugroho, A. (2016). Analysis of voltage drops and power losses in low-voltage networks using etap 12.6.0 software. Transient: Scientific Journal of Electrical Engineering, 5(1), 56–61.
[4] Kunang, S.O., Zuhriyadi, I., & Nugraha, A. (2017). Geographic Information System for Mapping Electricity Substations of Pt. PLN (Persero) South Sumatra Province. 255–260.
[5] Kurniawan, A. (2016). Voltage drop analysis and handling in the distribution network of 20 kv rayon channel pt. PLN (Persero) uses ETAP 12.6 scientific publications. 15.
[6] Marsudi, D. (2016). Electric Power System Operation Edition 3. Yogyakarta: Graha Ilmu .
[7] Nugraha, A., Yadi, I.Z., Firefly, S.O., Information Systems, M., Faculty, D., & Computer, I. (n.d.). Electricity Mapping of Pt Pln (Persero) South Sumatra Province Based on Geographic Information System (GIS).
[8] Improvement, S., Voltage, J., Loss, D., On, D., Voltage, J., With Development, R., Azzahra, S., Handayani, O., Auliya, S., Elektro, T., & Tinggi, S. (2019). PORTAL TYPE SUBSTATION. 8(1).
[9] PLN. (1995). SPLN. Jakarta: PLN
[10] PT, Persero, P.L.N., & Sunggal, U.L.P. (2019). Using the Mapsource application on Samuel Natanael Purba Electrical Engineering Study Program, Medan State Polytechnic.
[11] Samsurizal, S., & Makkulau, A. (2021). Modeling the recovery of a 500 kv system when a blackout occurs with a digsilent simulation. Shock: Control-Power-Electronics-Telecommunications-Computer Control Systems, 10(2).
[12] Sasongko, D.W., & Suyanto, M. (n.d.). 20 kV Distribution Network at Wonosari Substation Surakarta 74, Sasongko, Analysis of Losses in 20 kv Power Transformer Distribution Network at Wonosari-Surakarta Substation. 74–82.
[13] Suswanto, d. (2009). Electric Power Distribution System. Padang: Graha Ilmu
[14] Suprianto. (2018). Analysis of Falling Voltage on the 20 kV Distribution Network of PT. PLN Area Rantau Prapat Rayon Aek Batu City. Journal of Electrical Technology, 3(2), 64–72.
[15] Winardi, B., Winarno, H., & Aditama, K.R. (2016). Repair of Pwi 9 Voltage Losses and Drops by Transferring the Load to the New Pwi 11 Feeder at PT PLN (Persero) Semarang Area. Transmission, 18(2), 64–69.